PRODUCT LIST
Home > products > House wiring & equipment wire > House wiring & equipment wire
PVC insulated wire and cable with rated 450/750V and below
Applications
The product is designed for power equipments fixed wiring and flexible connection for electrical appliances
with A.C.rated voltage 450/750V and below.

Manufacturing standards
ASTM ICEA UL BS DIN IEC GB AS/NZS etc.

Types and description
Serial 
number
Type Description
60227 IEC 01(BV)  Single core rigid conductor unsheathed cable 
for general purposes(H07V-U or H07V-R) 
60227 IEC 02(RV)  Single core flexible conductor unsheathed cable
 for general purposes(H07V-U or H07V-R) 
60227 IEC 05(BV)  Single core 70℃ solid conductor unsheathed cable
 for internal wiring(H07V-U or H07V-R)
60227 IEC 06(RV)  Single core 70℃ flexible conductor unsheathed cable
 for internal wiring(H07V-K)
60227 IEC 07(BV-90)  Single core 90℃ solid conductor unsheathed cable 
for internal wiring(H07V-U or H07V-R)
60227 IEC 08(RV-90)  Single core 90℃ flexible conductor unsheathed cable
 for internal wiring(H07V-K)
60227 IEC 10(BVV)  Light PVC sheathed cable(NYY or NYM)                 
60227 IEC 42(RVB)  Flat unsheathed flexible wire                      
60227 IEC 52(RVV)  Light PVC sheathed flexible wire
(H03VV-F、H03VV2-F)           
10  60227 IEC 53(RVV)  Common PVC sheathed flexible wire
(H05VV-F、H05VV2-F)         
11  BV  Copper core PVC insulated wire(H07V-U or H07V-R)
12  B L V  Aluminum core PVC insulated wire
13  BVR  Copper core PVC insulated flexible cable(H07V-R)
14  BVV  Copper core PVC insulated sheathed
 circular cable(NYY or NYM)
15  BLVV  Aluminum core PVC insulated and sheathed round cable
16  BVVB  Copper core PVC insulated and sheathed flat cable
17  BLVVB  Aluminum core PVC insulated sheathed flat cable
18  NMD  Copper core PVC/Nylon Insulated PVC Jacked flat cable
19  RVS  Twisted copper core PVC insulated flexible cable for conection
20  AVP  Copper core PVC insulated wire with shied for installation
21  RVP  Copper core PVC insulated flexible wire with shield
22  RVVP Copper core PVC insulated, shieled, 
PVC sheathed flexible cable

Wire & Cable for Electrical Equipment

Specification and property
Table 1
Type Nom.
cross
section
mm2
No ./Dia.
 of
Strand
mm
Nom.
Thickness
of insulation
mm
Average
 OD(Max.)
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. Insulating
 resistance
at 70℃
MΩ·km
Copper
 core
Tinned 
copper
 core
60227 IEC 
01(BV) 450/750V
1.5 1/1.37 0.7 3.3 12.1 12.2 0.011
1.5 7/0.52 0.7 3.4 12.1 12.2 0.010
2.5 1/1.76 0.8 3.9 7.41 7.56 0.010
2.5 7/0.68 0.8 4.2 7.41 7.56 0.009
4 1/2.24 0.8 4.4 4.61 4.70 0.0085
4 7/0.85 0.8 4.8 4.61 4.70 0.0077
6 1/2.73 0.8 4.9 3.08 3.11 0.0070
6 7/1.04 0.8 5.4 3.08 3.11 0.0065
10 7/1.33 1.0 6.8 1.83 1.84 0.0065
16 7/1.70 1.0 8.0 1.15 1.16 0.0050
25 7/2.12 1.2 9.8 0.727 0.734 0.0050
35 7/2.50 1.2 11.0 0.524 0.529 0.0040
50 19/1.78 1.4 13.0 0.387 0.391 0.0045
70 18/2.12 1.4 15.0 0.268 0.270 0.0035
95 19/2.50 1.6 17.0 0.193 0.195 0.0035
120 37/2.00 1.6 19.0 0.153 0.154 0.0032
60227 IEC 01(BV) 
450/750V
150 37/2.24 1.8 21.0 0.124 0.126 0.0032
185 37/2.50 2.0 23.5 0.0991 0.100 0.0032
240 61/2.24 2.2 26.5 0.0754 0.0762 0.0032
300 61/2.50 2.4 29.5 0.0601 0.0607 0.0030
400 61/2.85 2.6 33.5 0.0470 0.0475 0.0028
60227 IEC 02(RV) 
450/750V
1.5 30/0.25 0.7 3.5 13.3 13.7 0.010
2.5 50/0.25 0.8 4.2 7.98 8.21 0.009
4 77/0.26 0.8 4.8 4.95 5.09 0.007
6 78/0.31 0.8 6.3 3.30 3.39 0.006
10 84/0.39 1.0 7.6 1.91 1.95 0.0056
16 133/0.39 1.0 8.8 1.21 1.24 0.0046
25 189/0.41 1.2 11.0 0.780 0.795 0.0044
35 259/0.41 1.2 12.5 0.554 0.565 0.0038
50 361/0.41 1.4 14.5 0.386 0.393 0.0037
70 337/0.51 1.4 17.0 0.272 0.277 0.0032
60227 IEC 
05(BV) 300/500V
0.5 1/0.80 0.6 2.4 36.0 36.7 0.015
0.75 1/0.97 0.6 2.6 24.5 24.8 0.012
1.0 1/1.13 0.6 2.8 18.1 18.2 0.011
60227 IEC 06(RV) 
300/500V
0.5 16/0.2 0.6 2.6 39.0 40.1 0.013
0.75 24/0.2 0.6 2.8 26.0 26.7 0.011
1.0 32/0.2 0.6 3.0 19.5 20.0 0.010
60227 IEC 07(BV-90) 300/500V 0.5 1/0.80 0.6 2.4 36.0 36.7 0.015
0.75 1/0.97 0.6 2.6 24.5 24.8 0.013
1.0 1/1.13 0.6 2.8 18.1 18.2 0.012
1.5 1/1.37 0.7 3.3 12.1 12.2 0.011
2.5 1/1.76 0.8 3.9 7.41 7.56 0.009
60227 IEC 08(RV-90) 300/500V 0.5 16/0.2 0.6 2.6 39.0 40.1 0.013
0.75 24/0.2 0.6 2.8 26.0 26.7 0.012
1.0 32/0.2 0.6 3.0 19.5 20.0 0.010
1.5 30/0.25 0.7 3.5 13.3 13.7 0.009
2 50/0.25 0.8 4.2 7.98 8.21 0.009
3453

Wire & Cable for Electric Equipment
Table 2
Type No . of cores
×Nom. Cross
Section
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of insulation
mm
Nom.
thickness
of sheath
mm
Average
 O.D.
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. Insulating
 resistance
at 70℃
MΩ·km
Min. Max. Copper 
core
Tinned
 copper 
core
60227 IEC
10(BVV)
300/500V
2×1.5 1/1.37 0.7 1.2 7.6 10.0 12.1 12.2 0.011
2×1.5 7/0.52 0.7 1.2 7.8 10.5 12.1 12.2 0.01
3×1.5 1/1.37 0.7 1.2 8.0 10.5 12.1 12.2 0.011
3×1.5 7/0.52 0.7 1.2 8.2 11.0 12.1 12.2 0.01
4×1.5 1/1.37 0.7 1.2 8.6 11.5 12.1 12.2 0.011
4×1.5 7/0.52 0.7 1.2 9.0 12.0 12.1 12.2 0.01
5×1.5 1/1.37 0.7 1.2 9.4 12.0 12.1 12.2 0.011
5×1.5 7/0.52 0.7 1.2 9.8 12.5 12.1 12.2 0.01
2×2.5 1/1.76 0.8 1.2 8.6 11.5 7.41 7.56 0.01
2×2.5 7/0.68 0.8 1.2 9.0 12.0 7.41 7.56 0.009
3×2.5 1/1.76 0.8 1.2 9.2 12.0 7.41 7.56 0.01
3×2.5 7/0.68 0.8 1.2 9.4 12.5 7.41 7.56 0.009
4×2.5 1/1.76 0.8 1.2 10.0 13.0 7.41 7.56 0.01
4×2.5 7/0.68 0.8 1.2 10.0 13.5 7.41 7.56 0.009
5×2.5 1/1.76 0.8 1.2 11.0 14.0 7.41 7.56 0.01
5×2.5 7/0.68 0.8 1.2 11.0 14.5 7.41 7.56 0.009
2×4 1/2.24 0.8 1.2 9.6 12.5 4.61 4.7 0.0085
2×4 7/0.85 0.8 1.2 10.0 13.0 4.61 4.7 0.0077
3×4 1/2.24 0.8 1.2 10.0 13.0 4.61 4.7 0.0085
3×4 7/0.85 0.8 1.2 10.5 13.5 4.61 4.7 0.0077
60227IEC10
(BVV)
300/500V
4×4 1/2.24 0.8 1.4 11.5 14.5 4.61 4.7 0.0085
4×4 7/0.85 0.8 1.4 12.0 15.0 4.61 4.7 0.0077
5×4 1/2.24 0.8 1.4 12.5 16.0 4.61 4.7 0.0085
5×4 7/0.85 0.8 1.4 13.0 17.0 4.61 4.7 0.0077
2×6 1/2.73 0.8 1.2 10.5 13.5 3.08 3.11 0.007
2×6 7/1.04 0.8 1.2 11.0 14.0 3.08 3.11 0.0065
3×6 1/2.73 0.8 1.4 11.5 14.5 3.08 3.11 0.007
3×6 7/1.04 0.8 1.4 12.0 15.5 3.08 3.11 0.0065
4×6 1/2.73 0.8 1.4 12.5 16.0 3.08 3.11 0.007
4×6 7/1.04 0.8 1.4 13.0 17.0 3.08 3.11 0.0065
5×6 1/2.73 0.8 1.4 13.5 17.5 3.08 3.11 0.007
5×6 7/1.04 0.8 1.4 14.5 18.5 3.08 3.11 0.0065
2×10 7/1.33 1.0 1.4 13.5 17.5 1.83 1.84 0.0065
3×10 7/1.33 1.0 1.4 14.5 19.0 1.83 1.84 0.0065
4×10 7/1.33 1.0 1.4 16.0 20.5 1.83 1.84 0.0065
5×10 7/1.33 1.0 1.4 17.5 22.0 1.83 1.84 0.0065
2×16 7/1.70 1.0 1.4 15.5 20.0 1.15 1.16 0.0052
3×16 7/1.70 1.0 1.4 16.5 21.5 1.15 1.16 0.0052
4×16 7/1.70 1.0 1.4 18.0 23.5 1.15 1.16 0.0052
5×16 7/1.70 1.0 1.6 20.5 26.0 1.15 1.16 0.0052
2×25 7/2.12 1.2 1.4 18.5 24.0 0.727 0.734 0.005
3×25 7/2.12 1.2 1.4 20.5 26.0 0.727 0.734 0.005
4×25 7/2.12 1.2 1.6 22.5 28.5 0.727 0.734 0.005
5×25 7/2.12 1.2 1.6 24.5 31.5 0.727 0.734 0.005
2×35 7/2.50 1.2 1.6 21.0 27.5 0.524 0.529 0.0044
3×35 7/2.50 1.2 1.6 22.0 29.0 0.524 0.529 0.0044
4×35 7/2.50 1.2 1.6 24.5 32.0 0.524 0.529 0.0044
5×35 7/2.50 1.2 1.6 27.0 35.0 0.524 0.529 0.0044
60227 IEC
42(RVB)
300/300V
2×0.5 28/0.15 0.8 - 2.5 5.0 3.0 6.0 39 40.1 0.016
2×0.75 42/0.15 0.8 - 2.7 5.4 3.2 6.4 26 26.7 0.014
60227 IEC
52(RVV)
300/300V
2×0.5 16/0.2 0.5 0.6 4.8 6.0 39 40.1 0.012
2×0.5 16/0.2 0.5 0.6 3.0 4.8 3.6 6.0 39 40.1 0.012
2×0.75 24/0.2 0.5 0.6 5.2 6.4 26 26.7 0.01
2×0.75 24/0.2 0.5 0.6 3.2 5.2 3.9 6.4 26 26.7 0.01
3×0.5 16/0.2 0.5 0.6 5.0 6.2 39 40.1 0.012
3×0.75 24/0.2 0.5 0.6 5.4 6.8 26 16.7 0.01

Wire & Cable for Electrical Equipment

Continue Table
Type No . of cores
×Nom. Cross
Section
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of insulation
mm
Nom.
thickness
of sheath
mm
Average O.D.
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. Insulating
 resistance
at 70℃
MΩ·km
Min. Max. Copper
 core
Tinned 
copper 
core
60227 IEC
53(RVV)
300/500V
2×0.75 24/0.2 0.6 0.8 6.0 7.6 26.0 26.7 0.011
2×0.75 24/0.2 0.6 0.8 3.8×6.0 5.2×7.6 26.0 26.7 0.011
2×1 32/0.2 0.6 0.8 6.4 8.0 19.5 20.0 0.010
2×1.5 30/0.25 0.7 0.8 7.4 9.0 13.3 13.7 0.010
2×2.5 50/0.25 0.8 1.0 8.9 11.0 7.98 8.21 0.009
3×0.75 24/0.2 0.6 0.8 6.4 8.0 26.0 26.7 0.011
3×1 32/0.2 0.6 0.8 6.8 8.4 19.5 20.0 0.010
3×1.5 30/0.25 0.7 0.9 8.0 9.8 13.3 13.7 0.010
3×2.5 50/0.25 0.8 1.0 9.6 12.0 7.98 8.21 0.009
4×0.75 24/0.2 0.6 0.8 6.8 8.6 26.0 26.7 0.011
4×1 32/0.2 0.6 0.9 7.6 9.4 19.5 20.0 0.010
4×1.5 30/0.25 0.7 1.0 9.0 11.0 13.3 13.7 0.010
4×2.5 50/0.25 0.8 1.1 10.5 13.0 7.98 8.21 0.009
5×0.75 24/0.2 0.6 0.9 7.4 9.6 26.0 26.7 0.011
5×1 32/0.2 0.6 0.9 8.3 10.0 19.5 20.0 0.010
5×1.5 30/0.25 0.7 1.1 10.0 12.0 13.3 13.7 0.010
5×2.5 50/0.25 0.8 1.2 11.5 14.0 7.98 8.21 0.009


Table 3
Type Nom.
cross
section
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of insulation
mm
Average 
OD(Max.)
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. Insulating 
resistance
at 70℃
MΩ·km
Copper core AL core Tinned
 copper 
core
BV
300/500V
0.75 7/0.37 0.6 2.6 24.5 - 24.8 0.014
1.0 7/0.43 0.6 2.8 18.1 - 18.2 0.013
BLV
450/750V
2.5 1/1.78 0.8 3.9   12.1   0.010
4 1/2.25 0.8 4.4   7.41   0.0085
6 1/2.76 0.8 5.0   4.61   0.0070
10 7/1.35 1.0 6.7   3.08   0.0065
16 7/1.70 1.0 7.8   1.91   0.0050
25 7/2.12 1.2 9.7   1.20   0.0050
35 7/2.50 1.2 10.9   0.868   0.0040
50 19/1.83 1.4 12.8   0.641   0.0045
70 19/2.12 1.4 14.6   0.443   0.0035
95 19/2.50 1.6 17.1   0.320   0.0035
120 37/2.0 1.6 18.8   0.253   0.0032
150 37/2.25 1.8 20.9   0.206   0.0032


Continue Table
Type Nom.
cross
section
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of insulation
mm
Average
 OD(Max.)
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. 
Insulating 
resistance
at 70℃
MΩ·km
Copper 
core
AL core Tinned
 copper
 core
B L V
450/750V
185 37/2.50 2.0 23.2   0.614   0.0032
240 61/2.25 2.2 26.6   0.125   0.0032
300 61/2.50 2.4 29.6   0.100   0.0030
400 61/2.85 2.6 33.2   0.0778   0.0028
B VR
450/750V
2.5 19/0.41 0.8 4.1 7.41   7.56 0.011
4 19/0.52 0.8 4.8 4.61   4.70 0.009
6 19/0.64 0.8 5.3 3.08   3.11 0.0084
10 49/0.52 1.0 6.8 1.83   1.84 0.0072
16 49/0.64 1.0 8.1 1.15   1.16 0.0062
25 98/0.58 1.2 10.2 0.727   0.734 0.0058
35 133/0.58 1.2 11.7 0.524   0.529 0.0052
50 133/0.68 1.4 13.9 0.387   0.391 0.0051
Table4
Type Nom.
Cross
 section
Con×
ductor
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of 
insulation
mm
Nom.
thickness
of sheath
mm
Average O.D
. mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. 
Insulating 
resistance
at 70℃
MΩ·km
Min. Max. Copper
core
AL
core
Tinned
copper 
core
BVV
300/500V
0.75 1/0.97 .06 0.8 3.6 4.4 24.5   24.8 0.012
1.0 1/1.13 0.6 0.8 3.6 4.4 18.1   18.2 0.011
1.5 1/1.37 0.6 0.8 3.7 4.5 12.1   12.2 0.011
1.5 7/0.52 0.7 0.8 4.2 5.0 12.1   12.2 0.010
2.5 1/1.76 0.7 0.8 4.3 5.2 7.41   7.56 0.010
2.5 7/0.68 0.8 0.8 4.8 5.7 7.41   7.56 0.009
4 1/2.24 0.8 0.9 4.8 5.9 4.61   4.7 0.0085
4 7/0.85 0.8 0.9 5.4 6.5 4.61   4.7 0.0077
6 1/2.73 0.8 0.9 5.5 6.8 3.08   3.11 0.0070
6 7/1.04 0.8 0.9 5.9 7.1 3.08   3.11 0.0065
10 7/1.33 0.8 0.9 6.0 7.3 1.83   1.84 0.0065
BLVV
300/500V
2.5 1/1.78 1.0 0.8 7.3 7.8   12.1   0.010
4 1/2.25 0.8 0.9 4.8 5.7   7.41   0.0085
6 1/2.76 0.8 0.9 5.4 6.5   4.61   0.0070
10 7/1.35 0.8 0.9 5.9 7.1   3.08   0.0065
Table5
Type No . of 
cores
Nom. Cross
Section
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of 
insulation
mm
Nom.
thickness
of sheath
mm
Average O.D
. mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. 
Insulating
 resistance
at 70℃
MΩ·km
Min. Max. Copper
core
AL
core
Tinned
copper
 core
BVVB
300/500V
2×0.75 1/0.97 0.6 0.9 3.8×5.9 4.6×7.1 24.5 - 24.8 0.012
2×1.0 1/1.13 0.6 0.9 3.9×6.1 4.8×7.4 18.1 - 18.2 0.011
2×1.5 /1.37 0.7 0.9 4.4×7.0 5.3×8.5 12.1 - 12.2 0.011
2×2.5 1/1.76 0.8 1.0 5.1×8.4 6.2×10.1 7.41 - 7.56 0.010
2×4 1/2.24 0.8 1.0 5.6×9.2 6.7×11.1 4.61 - 4.70 0.0085
2×4 7/0.85 0.8 1.0 5.7×9.5 6.9×11.5 4.61 - 4.70 0.0080
2×6 1/2.73 0.8 1.1 6.2×10.4 7.5×12.5 3.08 - 3.11 0.0070
2×6 7/1.04 0.8 1.1 6.4×10.8 7.8×13.0 3.08   3.11 0.0065
2×10 7/1.33 1.0 1.2 7.9×13.4 9.5×16.2 1.83 - 1.84 0.0065
3×0.75 1/0.97 0.6 0.9 3.8×7.9 4.6×9.6 24.5 - 24.8 0.012
3×1.0 1/1.13 0.6 0.9 3.9×8.4 4.8×10.1 18.1 - 18.2 0.011
3×1.5 /1.37 0.7 0.9 4.4×9.6 5.3×11.7 12.1 - 12.2 0.011
3×2.5 1/1.76 0.8 1.0 5.1×11.6 6.2×14.0 7.41 - 7.56 0.010
  3×4 1/2.24 0.8 1.1 5.8×13.1 7.0×15.8 4.61 - 4.70 0.0085

Wire & Cable for Electrical Equipment
Continue Table
Type No . of
 cores
Nom. Cross
Section
mm2
No ./Dia.
of strand
mm
Nom.
Thickness
of insulation
mm
Nom.
thickness
of sheath
mm
Average O.D
. mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. 
Insulating 
resistance
at 70℃
MΩ·km
Min. Max. Copper
core
AL
core
Tinned
copper 
core
BVVB
300/500V
3×4 7/0.85 0.8 1.1 5.9×13.5 7.1×16.3 4.61 - 4.70 0.0080
3×6 1/2.73 0.8 1.1 6.2×14.5 7.5×17.5 3.08 - 3.11 0.0070
3×6 7/1.04 0.8 1.1 6.4×15.1 7.8×18.2 3.08 - 3.11 0.0065
3×10 7/1.33 1.0 1.2 7.9×19.0 9.5×23.0 1.83 - 1.84 0.0065
BLVVB
450/750V
2 ×2.5 1/1.78 0.8 1.0 5.1×8.4 6.2×10.1 - 12.1 - 0.010
2×4 1/2.25 0.8 1.0 5.6×9.2 6.7×11.1 - 7.41 - 0.0085
2×6 1/2.76 0.8 1.1 6.2×10.4 7.5×12.5 - 4.61 - 0.070
2×10 7/1.35 1.0 1.2 7.9×13.4 9.5×16.2 - 3.08 - 0.0065
3  ×2.5 1/1.78 0.8 1.0 5.1×11.6 6.2×14.0 - 12.1 - 0.010
3×4 1/2.25 0.8 1.1 5.8×13.1 7.0×15.8 - 7.41 - 0.0085
3×6 1/2.76 0.8 1.1 6.2×14.5 7.5×17.5 - 4.61 - 0.0070
3×10 7/1.35 1.0 1.2 7.9×19.0 9.5×23.0 - 3.08 - 0.0065

NMD90,Copper,PVC/Nylon Insulated,PVC Jacked 90℃ 300V Table 6
Conductor Ground Wire Approx.
 Jacket 
Thickness
Approx.
Dimensions
Approx.
Weight
Ampacity
Amps
Size
AWG
No . of
Cores
No . of
strands
Insulation 
Thickness
Size
AWG
No . of
strands
mm in. mm in. Kg/km lbs/1000ft
mm in.
2 Two conductor
14 2 1 0.86 0.034 14 1 0.76 0.030 9.86×4.88 0.388×0.192 101 68 15
12 2 1 0.86 0.034 14 1 0.76 0.030 10.71×5.30 0.422×0.209 129 86 20
10 2 1 0.86 0.034 12 1 0.76 0.030 12.21×5.84 0.481×0.230 182 122 30
8 2 7 1.02 0.040 10 7 1.14 0.045 16.15×7.92 0.636×0.312 310 208 45
6 2 7 1.30 0.051 8 7 1.14 0.045 20.12×9.40 0.792×0.370 468 315 65
3 Three conductor
14 3 1 0.86 0.034 14 1 0.76 0.030 8.77 0.345 128 86 15
12 3 1 0.86 0.034 14 1 0.76 0.030 9.69 0.381 169 114 20
10 3 1 0.86 0.034 12 1 0.76 0.030 10.85 0.427 242 163 30
8 3 7 1.02 0.040 10 7 1.14 0.045 14.47 0.570 408 275 45
6 3 7 1.30 0.051 8 7 1.14 0.045 17.65 0.695 627 421 65
3 3 7 1.30 0.051 6 7 2.03 0.080 23.48 0.925 1189 799 105

Table 7
Type No . of cores
×Nom. Cross
section
mm2
No ./Dia.
of strand
mm
Nom.
 thickness
of insulation
mm
Average
 O.D.
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. Insulating
 resistance
at 70℃
MΩ·km
Copper core Tinned 
copper 
core
RVS 2 0.5 28 0.15 0.8 6.0 39.0 40.1 0.016
300/300V 2 0.75 42 0.15 0.8 6.2 26.0 26.7 0.014

Table 8
Type No . of
 cores
×Nom.
 Cross
section
mm2
No ./Dia.
of strand
mm
Nom. 
thickness
of 
insulation
mm
Dia.of single
wire of shield
mm
Average 
O.D.
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. 
Insulating 
resistance
at 70℃
MΩ·km
Copper
 core
Tinned 
copper 
core
AVP
300/300V
1×0.08 1/0.032 0.4 0.10 1.9 22.5.2 229.6 0.019
1×0.12 1/0.4 0.4 0.10 2.0 144.1 146.9 0.015
1×0.2 1/0.5 0.4 0.10 2.1 92.3 94.0 0.015
1×0.3 1/0.6 0.4 0.10 2.2 64.1 65.3 0.014
1×0.4 1/0.7 0.4 0.10 2.3 47.1 48.0 0.012

 

Wire & Cable for Electrical Equipment
Continue Table
 

 

Type No . of cores
×Nom. Cross
section
mm2
No ./Dia.
of strand
mm
Nom. 
thickness
of
 insulation
mm
Dia.of
 single
wire of
 shield
mm
Average O.D.
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min.
 Insulating
 resistance
at 70℃
MΩ·km
Copper 
core
Tinned 
copper 
core
RVP
300/300V
1×0.08 7/0.12 0.4 0.10 1.9 247 254 0.018
1×0.12 7/0.15 0.4 0.10 2.0 158 163 0.016
1×0.2 12/0.15 0.4 0.10 2.2 92.3 95.0 0.013
1×0.3 16/0.15 0.5 0.10 2.6 69.2 71.2 0.014
1×0.4 23/0.15 0.5 0.15 3.0 48.2 49.6 0.013
1×0.5 16/0.2 0.5 0.15 3.1 39.0 40.1 0.012
1×0.75 24/0.2 0.5 0.15 3.4 26.0 26.7 0.010
1×1.0 32/0.2 0.6 0.15 3.8 19.5 20.0 0.010
1×1.5 30/0.25 0.6 0.15 4.1 13.3 13.7 0.009
1×2.5 50/0.25 0.7 0.15 4.9 7.98 8.21 0.008
2×0.08 7/0.12 0.4 0.10 3.3/1.9×3.3 247 254 0.018
2×0.12 7/0.15 0.4 0.10 3.5/2.0×3.5 158 163 0.016
2×0.2 12/0.15 0.4 0.10 3.9/2.2×3.9 92.3 95.0 0.013
2×0.3 16/0.15 0.5 0.10 4.8/2.8×4.8 69.2 71.2 0.014
2×0.4 23/0.15 0.5 0.15 5.2/3.0×5.2 48.2 49.6 0.013
2×0.5 16/0.2 0.5 0.15 5.4/3.1×5.4 39.0 40.1 0.012
2×0.75 24/0.2 0.5 0.15 6.0/3.4×6.0 26.0 26.7 0.010
2×1.0 32/0.2 0.6 0.15 6.8/3.8×6.8 19.5 20.0 0.010
2×1.5 30/0.25 0.6 0.15 7.4/4.1×7.4 13.3 13.7 0.009


Table 9
 

 

Type No . of 
cores
Nom. 
Cross
Section
mm2
No ./Dia.
of strand
mm
Dia.of 
single
wire of
 shield
mm
Nom.
Thickness
of 
insulation
mm
Nom.
thickness
of 
sheath
mm
Average O.D.
mm
Max.DC 
conductor
resistance
 at 20℃
Ω/km
Min.
 Insulating
 resistance
at 70℃
MΩ·km
Min. Max. Copper
core
Tinned
copper
 core
RVVP
300/300V
1×0.08 0.13 0.10 0.4 0.4 2.4 2.9 247 254 0.018
1×0.12 0.16 0.10 0.4 0.4 2.4 3.0 158 163 0.016
1×0.2 0.16 0.10 0.4 0.4 2.6 3.2 92.3 95.0 0.013
1×0.3 0.16 0.10 0.5 0.4 2.9 3.5 69.2 71.2 0.14
1×0.4 0.16 0.10 0.5 0.4 3.0 3.7 48.2 49.6 0.013
1×0.5 0.21 0.10 0.5 0.4 3.1 3.8 39.0 40.1 0.012
1×0.75 0.21 0.10 0.5 0.4 3.4 4.1 26.0 26.7 0.010
1×1.0 0.21 0.10 0.6 0.6 4.1 4.9 19.5 20.0 0.010
1×1.5 0.26 0.10 0.6 0.6 4.3 5.2 13.3 13.7 0.009
1×2.5 0.26 0.15 0.6 0.6 4.9 6.0 7.98 8.21 0.008
2×0.08 0.13 0.10 0.4 0.4 3.2/2.4×3.5 4.2/2.9×4.2 247 254 0.018
2×0.12 0.16 0.10 0.4 0.6 3.7/2.8×4.0 4.9/3.4×4.9 158 163 0.016
2×0.2 0.16 0.10 0.4 0.6 4.1/3.0×4.4 5.3/3.6×5.3 92.3 95.0 0.013
2×0.3 0.16 0.15 0.5 0.6 4.8/3.5×5.1 6.2/4.2×6.2 69.2 71.2 0.14
2×0.4 0.16 0.15 0.5 0.6 5.1/3.6×5.4 6.6/4.4×6.6 48.2 49.6 0.013
2×0.5 0.21 0.15 0.5 0.6 5.3/3.7×5.6 6.8/4.5×6.8 39.0 40.1 0.012
2×0.75 0.21 0.15 0.5 0.6 5.8/4.0×6.1 7.4/4.8×7.4 26.0 26.7 0.010
2×1.0 0.21 0.15 0.6 0.6 6.4/4.3×6.7 8.2/5.2×8.3 19.5 20.0 0.010
2×1.5 0.26 0.15 0.6 0.8 7.3/4.9×7.6 9.2/6.0×9.3 13.3 13.7 0.009
3×0.12 0.16 0.10 0.4 0.6 3.9 5.1 158 163 0.016
3×0.2 0.16 0.15 0.4 0.6 4.5 5.8 92.3 95.0 0.013
3×0.3 0.16 0.15 0.5 0.6 5.1 6.5 69.2 71.2 0.014
3×0.4 0.16 0.15 0.5 0.6 5.4 6.9 48.2 49.6 0.013
3×0.5 0.21 0.15 0.5 0.6 5.6 7.1 39.0 40.1 0.012
3×0.75 0.21 0.15 0.5 0.6 6.1 7.8 26.0 26.7 0.010
3×1.0 0.21 0.15 0.6 0.8 7.2 9.1 19.5 20.0 0.010
3×1.5 0.26 0.20 0.6 0.8 8.0 10.0 13.3 13.7 0.009
4×0.12 0.16 0.15 0.4 0.6 4.5 5.8 158 163 0.016
4×0.2 0.16 0.15 0.4 0.6 4.9 6.2 92.3 95.0 0.013
4×0.3 0.16 0.15 0.5 0.6 5.5 7 69.2 71.2 0.014
4×0.4 0.16 0.15 0.5 0.6 5.9 7.5 48.2 49.6 0.013
5×0.12 0.16 0.15 0.4 0.6 4.8 6.2 158 163 0.016
5×0.2 0.16 0.15 0.4 0.6 5.3 6.7 92.3 95.0 0.013
5×0.3 0.16 0.15 0.5 0.6 6.0 7.6 69.2 71.2 0.014
5×0.4 0.16 0.15 0.4 0.6 6.4 8.1 48.2 49.6 0.013
6×0.12 0.16 0.15 0.4 0.6 5.2 6.6 158 163 0.016
6×0.2 0.16 0.15 0.4 0.6 5.7 7.2 92.3 95.0 0.013

Wire & Cable for Electrical Equipment
Continue Table


Type No . of
 cores
Nom.
 Cross
Section
mm2
No ./Dia.
of strand
mm
Dia.of 
single
wire of 
shield
mm
Nom.
Thickness
of 
insulation
mm
Nom.
thickness
of sheath
mm
Average O.D.
mm
Max.DC conductor
resistance at 20℃
Ω/km
Min. Insulating
 resistance
at 70℃
MΩ·km
Min. Max. Copper
core
Tinned
copper core
RVVP
300/300V
6×0.3 0.16 0.15 0.5 0.7 6.5 8.2 69.2 71.2 0.014
6×0.4 0.16 0.15 0.5 0.8 7.3 9.2 48.2 49.6 0.013
7×0.12 0.16 0.15 0.4 0.6 5.2 6.6 158 163 0.016
7×0.2 0.16 0.15 0.4 0.6 5.7 7.2 92.3 95.0 0.013
7×0.3 0.16 0.15 0.5 0.6 6.5 8.2 69.2 71.2 0.014
7×0.4 0.16 0.15 0.5 0.8 7.3 9.2 48.2 49.6 0.013
10×0.12 0.16 0.15 0.4 0.6 6.4 8.1 158 163 0.016
10×0.2 0.16 0.15 0.4 0.8 7.4 9.3 92.3 95.0 0.013
10×0.3 0.16 0.20 0.5 0.8 8.7 10.9 69.2 71.2 0.014
10×0.4 0.16 0.20 0.5 0.8 9.3 11.6 48.2 49.6 0.013
12×0.12 0.16 0.15 0.4 0.6 6.6 8.3 158 163 0.016
12×0.2 0.16 0.15 0.4 0.8 7.6 9.6 92.3 95.0 0.013
12×0.3 0.16 0.20 0.5 0.8 9.0 11.2 69.2 71.2 0.014
12×0.4 0.16 0.20 0.5 0.8 9.6 11.9 48.2 49.6 0.013
14×0.12 0.16 0.15 0.4 0.8 7.2 9.1 158 163 0.016
14×0.2 0.16 0.20 0.4 0.8 8.2 10.3 92.3 95.0 0.013
14×0.3 0.16 0.20 0.5 0.8 9.4 11.7 69.2 71.2 0.014
14×0.4 0.16 0.20 0.5 0.8 10.0 9.5 48.2 49.6 0.013
16×0.12 0.16 0.15 0.4 0.8 7.6 10.8 158 163 0.016
16×0.2 0.16 0.20 0.4 0.8 8.6 12.3 92.3 95.0 0.013
16×0.3 0.16 0.20 0.5 0.8 9.9 13.1 69.2 71.2 0.014
16×0.4 0.16 0.20 0.5 0.8 10.5 11.3 48.2 49.6 0.013
19×0.12 0.16 0.20 0.4 0.8 8.2 10.3 158 163 0.016
19×0.2 0.16 0.20 0.4 0.8 9.0 11.3 92.3 95.0 0.013
19×0.3 0.16 0.20 0.5 0.8 10.4 12.9 69.2 71.2 0.014
19×0.4 0.16 0.20 0.5 1.0 11.5 14.2 48.2 49.6 0.013
24×0.12 0.16 0.20 0.4 0.8 9.4 11.7 158 163 0.016
24×0.2 0.16 0.20 0.4 0.8 10.4 12.9 92.3 95.0 0.013
24×0.3 0.16 0.20 0.5 1.0 12.4 14.4 69.2 71.2 0.014
24×0.4 0.16 0.20 0.5 1.0 13.2 16.4 48.2 49.6 0.013

 

    Design by JUSI Network© 2013 Jiangsu Ganghong Electric Wire & Power Cable Co., Ltd. All Rights Reserved.