PRODUCT LIST
Home > Products > Control Cable > Control Cable
Flame resistance plastic insulated control cable
Flame Resistance Plastic Insulated Control Cable

Application
The cables are designed for connection wires of power distribution equip-ments for controlling, monitoring, protecting
circuits with A .C. rated voltage 450/750V and below.
Manufacturing standards
ASTM ICEA BS DIN IEC GB AS/NZS etc.
Operating features
2.1  Rated voltage Uo/U is 450/750V.
2.2  Allowed continuous working temperature of conductor is 70℃ .
2.3  Installation temperature of cables should be no less than 0℃ . Bending radius should be not less than 10 times O.D. of cable.
Type,description and main application Table 1
Type Description Main Application
KVV-C Copper conductor PVC insulated 
and PVC sheathed control cable
For fixed installation,laying indoors,
in trenches, in ducts
ZR-KVV-C Copper conductor PVC insulated 
and sheathed flame resistance 
control cable
KVVP-C Copper conductor PVC insulated 
and sheathed control cable with 
braiding screen
Laying indoors, in trenches
in ducts where screen
requested
ZR-KVVP-C Copper conductor PVC insulated 
and sheathed flame resistance
 control cable with braiding screen
KVVR-C Copper conductor PVC insulated 
and PVC sheathed flexible control cable
For fixed installation, laying
indoors, in trenches, in ducts
where flexibility requested
ZR-KVVR-C Copper conductor PVC insulated 
and sheathed flame resistance 
flexible control cable
KVVRP-C Copper conductor PVC insulated
 and sheathed flexible control
 cable with braiding screen
Laying indoors, in trenches
in ducts where flexibility,
screen requested
ZR-KVVRP-C Copper conductor PVC insulated
 and sheathed flame resistance
 flexible control cable with braiding screen

Specification Table2
Type Rated
voltage
V
Nom.area of conductor (mm2)
0.75 1.0 1.5 2.5 4 6 10 16
No .of cores
450/750 KVV-C 2~61 2~10 2~4
ZR-KVV-C
KVVP-C
ZR-KVVP-C
KVVR-C
ZR-KVVR-C
VVRP-C
KVVRP-C


Flame Resistance Plastic Insulated Control Cable

Main technical requirements
5.1 Conductor Conductor construction and D.C.Resistance should be in accordance with Table 3
5.2 Insulation
Insulated core should be identified with different colors or different number.Nominal wall thickness of insulation should be in accordance with table 3, and the thinnest point should be not less than 90%-0.1mm of Nom. value.Min. Insulation resistance at 70 should be in accordance with the stipulations of table 4.
5.3 Finished cable should withstand voltage withstanding test with AC 50Hz,3000V,5 minutes.

Construction of conductor Table3
Nom. 
Cross 
Sectional
mm2
Construction 
of conductor
DC Resistance 
of conductor
 at 20℃ (Max.)
Ω/km
Nom. wall
 thickness
of insulation
mm
Min lnsulation
 resistance at
 70℃ MΩ·km
Category No./Nom.Dia
 of strand
mm
0.75  1/0.97  24.5  0.8  40 
0.75  7/0.37  24.5  0.8  40 
1.0  1/1.13  18.1  0.8  40 
1.0  7/0.43  18.1  0.8  40 
1.5  1/1.38  12.1  0.8  40 
1.5  7/0.52  12.1  0.8  40 
2.5  1/1.78  7.41  0.8  20 
2.5  7/0.68  7.41  0.8  20 
1/2.25  4.61  0.8  20 
7/0.85  4.61  0.8  20 
1/2.76  3.08  1.0  20 
7/1.04  3.08  1.0  20 
10  7/1.35  1.83  1.0  20 
10  19/0.82  1.83  1.0  20 
16  7/1.68  1.15  1.0  20 
16  49/0.64  1.15  1.0  20 
Note:KVV-C ZR-KVV-C adopts category “1” conductor, while other types adopt category “2 ”conductor