PRODUCT LIST
Home > Products > Control Cable > Control Cable
VDE standard control cable part1
YY PVC/PVC Number Coded Control Cable

Application: designed to offer a flexible solution for signalling, measuring and control applications. 
This range of cables are not only flexible but offer heat and oil protection.
Standards: Generally to BS6500 and VDE0250
Conductor: Flexible class 5 copper conductors to BS6360/VDE0295
Insulation: PVC
Sheath:PVC
Voltage Rating: 300/500V
Temperature rating: Flexing -15 to +70℃
Static -35 to +70℃
Minimum bending radius: 6 x overall diameter
Core identification: Black with White numbers. (3 core and above to include Green/Yellow) Coloured cores available on request

Current Carrying Capacity (amperes)
Nominal Cross Sectional Area  Single Phase AC or DC  Three Phase AC 
mm2  Amps  Amps 
0.75 
1.0  10  10 
1.5  16  16 
2.5  25  20 
4.0  32  25 
6.0  51  43 
10.0  70  60 
16.0  94  80 

For ambient air temperatures other than 30℃ the following rating factors should be applied:
Ratings for cables up to and including 4mm2 are based on 60℃ conductor operating temperature with 
6mm2 and above based on 70℃ operating temperature.
Correction Factors:
Cables Up To and Including 4mm2 , Assuming 60℃  Conductor Temperature.
Ambient Temperature  35℃ 40℃  45℃  50℃  55℃ 
Correction Factor  0.91  0.82  0.71  0.58  0.41 

VDE Standard Control Cable
YY PVC/PVC Number Coded Control Cable
Cables 6mm2  and above, Assuming 70℃ Conductor Temperature
Ambient Temperature  35℃ 40℃  45℃  50℃  55℃  60℃
Correction Factor  0.91  0.82  0.71  0.58  0.41 0.50

Part NO . Number
 of 
Cores
Nominal 
Cross 
Sectional
 Area 
mm2
No . /Nominal 
Diameter 
of Strands 
mm
Nominal 
Overall 
Diameter 
mm
Nominal 
Weight 
kg/km
GH-CT-YY-3C0.75SQ 3 0.75 24/0.20 5.9 55
GH-CT-YY-3C1.00SQ 3 1 32/0.20 6.4 67
GH-CT-YY-3C1.50SQ 3 1.5 30/0.25 7.4 92
GH-CT-YY-3C2.50SQ 3 2..5 50/0.25 9.5 153
GH-CT-YY-3C4.00SQ 3 4 56/0.30 12 235
GH-CT-YY-3C6.00SQ 3 6 84/0.30 12.8 305
GH-CT-YY-3C10.0SQ 3 10 80/0.40 15.8 590
GH-CT-YY-3C16.0SQ 3 16 126/0.40 18.4 800
GH-CT-YY-4C0.75SQ 4 0.75 24/0.20 6.8 76
GH-CT-YY-4C1.00SQ 4 1 32/0.20 7.4 89
GH-CT-YY-4C1.50SQ 4 1.5 30/0.25 8.5 122
GH-CT-YY-4C2.50SQ 4 2.5 50/0.25 10.4 191
GH-CT-YY-4C4.00SQ 4 4 56/0.30 13.5 330
GH-CT-YY-4C6.00SQ 4 6 84/0.30 16 480
GH-CT-YY-4C10.0SQ 4 10 80/0.40 20.8 743
GH-CT-YY-4C16.0SQ 4 16 126/0.40 24.1 1104
GH-CT-YY-5C0.75SQ 5 0.75 24/0.20 7.4 88
GH-CT-YY-5C1.00SQ 5 1 32/0.20 8.1 108
GH-CT-YY-5C1.50SQ 5 1.5 30/0.25 9.3 148
GH-CT-YY-5C2.50SQ 5 2.5 50/0.25 11.7 241
GH-CT-YY-5C4.00SQ 5 4 56/0.30 14.7 404
GH-CT-YY-5C6.00SQ 5 6 84/0.30 17.2 592
GH-CT-YY-5C10.0SQ 5 10 80/0.40 22.9 920
GH-CT-YY-5C16.0SQ 5 16 126/0.40 28.4 1370
GH-CT-YY-7C0.75SQ 7 0.75 24/0.20 8 113
GH-CT-YY-7C1.00SQ 7 1 32/0.20 8.8 140
GH-CT-YY-7C1.50SQ 7 1.5 30/0.25 10.1 193
GH-CT-YY-7C2.50SQ 7 2.5 50/0.25 12.9 311
SY PVC/PVC/GSWB/PVC Control Cable

Application:
 For use as a measuring, control and signal cable for the 
machine tool industry, plant construction, heating and air conditioning, 
and as a flexible cable between fixed and mobile equipment. The cable is 
well protected against mechanical damage by the narrow weave steel-wire braid.
· Note:should not be used in any installations where the cable is subjected to repetitive flexing.
Standards: Generally BS6500 VDE0250
Conductor: Class 5 annealed copper conductors to BS6360/VDE0295
Current Carrying Capacity (amperes)
Insulation: PVC
Bedding: PVC
Braiding: Galvanized Steel Wire Braid (GSWB)
Sheath: PVC (Type TM2 to BS7655)
Voltage Rating: 300/500V
Temperature rating: Flexing -15 to +70℃ , Staic -35 to +70℃
Minimum bending radius: 6 x overall diameter
Core identification: Black with White numbers. (3 core and above to include
 Green/Yellow) Coloured cores available on request
Nominal Cross Sectional Area Single Phase AC or DC Three Phase AC
mm2 Amps Amps
0.5 3 3
0.8 6 6
1.0 10 10
1.5 16 16
2.5 25 20
4.0 32 25
6.0 51 43
10.0 70 60
16.0 94 80

For ambient air temperatures other than 30℃ the following rating factors should be applied:
Ratings for cables up to and including 4mm2 are based on 60℃ conductor operating temperature 
with 6mm2 and above based on 70℃ operating temperature.
Correction Factors:
Cables Up To and Including 4mm2 , Assuming 60 Conductor Temperature.
Ambient Temperature  35℃ 40℃  45℃  50℃  55℃ 
Correction Factor  0.91  0.82  0.71  0.58  0.41

VDE Standard Control Cable
SY PVC/PVC/GSWB/PVC Control Cable

Cables 6mm2 and above, Assuming 70℃ Conductor Temperature
Ambient Temperature  35℃ 40℃  45℃  50℃  55℃  60℃
Correction Factor  0.91  0.82  0.71  0.58  0.41 0.50

Part NO . Number 
of Cores
Nominal 
Cross 
Sectional 
Area 
mm2
No . /Nominal 
Diameter of 
Strands 
mm
Nominal 
Overall 
Diameter 
mm
Nominal 
Weight 
kg/km
GH-CT-SY-3C1.00SQ  32/0.20  142 
GH-CT-SY-3C1.50SQ  1.5  30/0.25  10.2  186 
GH-CT-SY-3C2.50SQ  2.5  50/0.25  11.9  246 
GH-CT-SY-3C4.00SQ  56/0.30  15.1  330 
GH-CT-SY-3C6.00SQ  84/0.30  16.2  407 
GH-CT-SY-3C10.0SQ  10  80/0.40  20.1  621 
GH-CT-SY-3C16.0SQ  16  126/0.40  23.8  857 
GH-CT-SY-4C1.00SQ  32/0.20  9.8  165 
GH-CT-SY-4C1.50SQ  1.5  30/0.25  10.9  212 
GH-CT-SY-4C2.50SQ  2.5  50/0.25  13.4  315 
GH-CT-SY-4C4.00SQ  56/0.30  16.4  457 
GH-CT-SY-4C6.00SQ  84/0.30  19.5  687 
GH-CT-SY-4C10.0SQ  10  80/0.40  24.2  1009 
GH-CT-SY-4C16.0SQ  16  126/0.40  27.1  1384 
GH-CT-SY-5C1.00SQ  32/0.20  10.5  197 
GH-CT-SY-5C1.50SQ  1.5  30/0.25  11.7  241 
GH-CT-SY-5C2.50SQ  2.5  50/0.25  14.5  365 
GH-CT-SY-5C4.00SQ  56/0.30  17.7  545 
GH-CT-SY-5C6.00SQ  84/0.30  21.1  798 
GH-CT-SY-5C10.0SQ  10  80/0.40  26.2  1197 
GH-CT-SY-5C16.0SQ  16  126/0.40  30.6  1740 
GH-CT-SY-7C1.00SQ  32/0.20  11.2  231 
GH-CT-SY-7C1.50SQ  1.5  30/0.25  13.1  310 
GH-CT-SY-7C2.50SQ  2.5  50/0.25  15.5  458 