XLPE power cable with or without armoring part4
Continuous current capacity of single core XLPE insulated power cable with rated voltage 18/30kV to 26/35kV
Type YJV  YJLY  YJY  YJLY 
Arrange 
type 
Delta(connect 
each other) 
Flat(the space betweem 
adjacent cores is the 
overall diameter of cable) 
Laying method
Nominal cross section 
area(mm2) 
In air  Direct buired  In air  Direct buired 
Cu  Al  Cu  Al  Cu  Al  Cu  Al 
50  215  170  260  200  250  190  225  175 
70  270  210  320  250  305  240  275  215 
95  330  255  390  300  375  290  335  260 
120  380  295  445  345  435  335  380  295 
150  430  330  500  395  490  380  425  330 
185  490  380  570  440  565  435  485  375 
240  575  450  665  515  665  520  565  435 
300  660  515  750  585  760  590  635  495 
400  765  600  867  680  890  695  730  570 
500  875  695  980  775  1030  810  830  655 
630  1010  810  1110  895  1200  950  950  755 
800  1150  940  1250  1020  1380  1110  1080  865 
1000  1260  1050  1360  1130  1540  1250  1190  960 
Ambient temperature 40 ℃ 25℃  40 ℃ 25 ℃
Operating temperature  90℃
1)Reference continuous current capacity of steel wire armoured single-core cable is 65% of that of non-armoured single-core cable.
2)The moisture in soil is not considered.The soil thermal resistivity ρ w=1.0℃ m/W.See following table for correction coefficient of reference current carrying capacity.
3)One end of metal screen shall be earthed.

Continuous current capacity of three-core XLPE insulated power cable with rated voltage 18/30kV to 26/35kV
Type YJV  YJLY  YJY  YJLY YJV22 YJLV22 YJV32 YJLV32 
YJV42 YJLV42YJY22 YJLY22 
YJY32 YJY32 YJLY42 YJLY42
Laying method
Nominal cross
 section area(mm2) 
In air  Direct buired  In air  Direct buired 
Cu  Al  Cu  Al  Cu  Al  Cu  Al 
335  150  115  160  125  150  115  160  125 
350  180  140  190  145  180  140  190  145 
370  220  170  230  180  220  170  230  180 
395  265  205  275  215  265  205  275  215 
3 120  305  235  315  245  310  240  315  245 
3 150  345  270  355  275  350  270  355  275 
3 185  390  305  400  310  400  310  400  310 
3 240  455  355  460  360  465  360  460  360 
3 300  525  410  520  410  535  420  520  410 
3 400  600  470  590  465  615  485  590  465 
Ambient temperature  40 ℃ 25 ℃ 40 ℃ 25 ℃
Operating temperature  90℃
1)The moisture in soil is not considered.The soil thermal resistivity ρ w=1.0℃  m/W.See following table for correction coefficient  of reference current carrying capacity.
2)Cable is installed separately,the adjacent cable has no thermal effect on each other.
Continuous current capacity of single core XLPE insulated power cable with rated voltage 3.6/6kV to 12/20kV
Type YJV  YJLY  YJY  YJLY 
Arrange type  Delta(connect 
each other) 
Flat(the space betweem 
adjacent cores is the overall 
diameter of cable) 
Laying method
Nominal cross 
section area(mm2 ) 
In air  Direct buired  In air  Direct buired 
Cu  Al  Cu  Al  Cu  Al  Cu  Al 
25  145  110  185  145  170  130  160  125 
35  175  135  225  175  205  160  190  150 
50  210  160  270  210  245  190  230  175 
70  260  200  330  255  310  240  280  215 
95  320  245  400  310  380  295  335  260 
120  370  285  460  345  440  340  385  295 
150  420  325  520  400  500  385  430  335 
185  460  375  585  455  570  445  490  380 
240  565  440  680  530  675  525  565  440 
300  650  510  775  605  780  610  640  500 
400  755  595  885  700  910  710  735  575 
500  865  690  1000  795  1050  825  835  660 
630  1000  810  1140  920  1230  970  960  760 
800  1140  940  1270  1040  1420  1140  1080  865 
1000  1250  1050  1370  1150  1580  1290  1180  970 
Ambient temperature 40 ℃ 25 ℃ 40 ℃ 25 ℃
Operating temperature  90℃
1) Reference continuous current capacity of steel wire armoured single-core cable is 65% of that of non-armoured single-core
cable.
2) The moisture in soil is not considered.The soil thermal resistivityρ w=1.0℃ m/W.See following table for correction coefficient of reference current carrying capacity.
3) One end of metal screen shall be earthed.

Continuous current capacity of three-core XLPE insulated power cable with rated voltage 18/30kV to 26/35kV
Type YJV  YJLY  YJY  YJLY YJV22 YJLV22 YJV32 YJLV32 
YJV42 YJLV42YJY22 YJLY22 
YJY32 YJY32 YJLY42 YJLY42
Laying method
Nominal cross 
section area(mm2) 
In air  Direct buired  In air  Direct buired 
Cu  Al  Cu  Al  Cu  Al  Cu  Al 
325  120  96  135  105  120  90  135  105 
335  150  115  160  125  145  110  160  125 
350  175  135  190  150  170  130  190  150 
370  220  170  235  185  210  165  235  185 
395  265  205  285  220  265  200  285  220 
3 120  305  235  320  250  300  235  320  250 
3 150  350  270  365  285  340  265  365  285 
3 185  395  310  410  320  390  305  410  320 
3 240  465  365  475  370  455  355  475  370 
3 300  530  415  535  420  520  410  535  420 
3 400  615  485  605  480  600  475  605  480 
Ambient temperature  40 ℃ 25 ℃ 40 ℃ 25 ℃
Operating temperature  90℃
Correction coefficient of current-carrying capacity under different ambient temperature.(in air)
Operating 
temperature 
of conductor (℃)
Ambient temperature(in air) (℃)
10 15 20 25 30 35 40 45 50
60 1.58 1.50 1.41 1.32 1.22 1.11 1.00 0.86 0.73
65 1.48 1.41 1.34 1.26 1.18 1.09 1.00 0.89 0.77
70 1.41 1.35 1.29 1.22 1.15 1.08 1.00 0.91 0.81
80 1.32 1.27 1.22 1.17 1.11 1.06 1.00 0.93 0.86
90 1.26 1.22 1.18 1.14 1.09 1.04 1.00 0.94 0.89
105 1.22 1.19 1.15 1.11 1.08 1.04 1.00 0.95 0.91

Correction coefficient of current-carrying capacity under different ambient temperature.(in soil)
Operating 
temperature 
of conductor (℃)
Ambient temperature(in Soil) (℃)
10 15 20 25 30 35
60 1.20 1.13 1.07 1.00 0.93 0.85
65 1.17 1.12 1.06 1.00 0.94 0.87
70 1.15 1.11 1.05 1.00 0.94 0.88
80 1.13 1.09 1.04 1.00 0.95 0.90
90 1.11 1.07 1.04 1.00 0.96 0.92

Correction coefficient of cu rrent-carrying capacity for di fferent thermal resistivity.
Voltage Sectional area ρt( ℃.m/w) Thermal resistivity
(kV) (mm2 ) 0.8 1.0 1.2 1.5 2.0
3.6/6~6/6 ≤35
50~150
≥185
1.06
1.08
1.09
1.00
1.00
1.00
0.95
0.94
0.93
0.88
0.87
0.85
0.80
0.77
0.76
6/10~12/15 ≤35
50~150
≥185
1.05
1.06
1.07
1.00
1.00
1.00
0.95
0.94
0.93
0.89
0.88
0.86
0.80
0.79
0.77
12/20~26/35 ≤95
≥120
1.05
1.06
1.00
1.00
0.95
0.94
0.90
0.83
0.82
0.80
Correction coefficient of current-carrying for multi-cable laid in parallel in air.
Array Layer no . Layer×Pcs Gap between 
cables/cables 
Dia. D/De
Correction
 factor of
 current
 rating
Note
Level Vertical
rray of 
muti-cable
  1×2 - <5 0.89 D=Gap between cables;
De=Outer Dia.of cables
Array legend
one layer:1×3

Two layers:2×2

Three layers:3×3
1×3 - <0.75 0.84
Two 2×1 <0.5 1.9~1.5 0.99
1.4~1.0 0.97
<0.5 0.90
2×2 <0.5 2~1.5 0.99
1.49~1.5 0.97
0.9~0.5 0.90
Three 3×1 - 4~3 0.99
2.9~2.0 0.97
1.9~1.0 0.94
<0.5 .85
3×2
3×3
<0.5 
<0.75
4~3 0.99
2.9~2.0 0.97
1.9~1.0 0.94
<0.5 0.85

Max.calculated permissible short-circuit current of conductor.
Nominal cross-sectional area of 
conductor mm2
Maximum permissible short-circuit current f conductor(1 second)
KA
Copper conductor Aluminum conductor
10 1.51 0.988
16 2.39 1.56
25 3.69 2.42
35 5.15 3.37
50 7.31 4.79
70 10.2 6.68
95 13.8 9.03
120 17.4 11.4
150 21.7 14.2
185 26.7 17.5
240 34.6 22.6
300 43.1 28.2
400 57.4 37.6
500 71.7 47.0
630 88.8 58.0


Max.permissible short-circuit current for metallic screen(copper tape screen)
Single-core cable
Nominal cross-section of conductor mm2 Rated voltages of cable(kV)
12/20 18/30 21/35 26/35
Short-circuit current A
35 - - - -
50 1096 - - -
70 1095 1284 1286 1288
95 1091 1281 1285 1286
120 1272 1280 1284 1283
150 1271 1279 1280 1282
185 1270 1278 1279 1282
240 1267 1275 1279 1279
300 1266 1274 1276 1278
400 1265 1271 1275 1277
500 1260 1270 1272 1274
630 1257 1266 1272 1273
35 1253 1265 1270 1270

Capacitance of cable(reference value)
Nominal cross-section of conductor mm2 Rated voltages of cable(kV)
12/20 18/30 21/35 26/35
Capacitance for each phase μF/km
25 0.1378 0.1163 0.1064 0.0992
35 0.1502 0.1251 0.1140 0.1061
50 0.1661 0.1363 0.1239 0.1150
70 0.1868 0.1508 0.1365 0.1263
95 0.2060 0.1643 0.1483 0.1368
120 0.2228 0.1760 0.1584 0.1460
150 0.2418 0.1893 0.1700 0.1563
185 0.2656 0.2060 0.1815 0.1665
240 0.2916 0.2207 0.1972 0.1805
300 0.3175 0.2387 0.2128 0.1745
400 0.3551 0.2648 0.2354 0.2146
500 0.3880 0.2876 0.2551 0.2321
630 0.4278 0.3151 0.2789 0.2533

Inductance for single-core cable.(reference value)
Nominal cross-section of conductor mm2 Rated voltages of cable(kV)
12/20 18/30 21/35 26/35
Inductance  μH/km
25 0.6621 0.7006 0.7168 0.7273
35 0.6390 0.6762 0.6942 0.7021
50 0.6145 0.6501 0.6675 0.6751
70 0.5919 0.5252 0.6394 0.6467
95 0.5726 0.6043 0.6180 0.6279
120 0.5586 0.5891 0.6051 0.6118
150 0.5449 0.5740 0.5895 0.5959
185 0.5351 0.5640 0.5760 0.5839
240 0.5216 0.5487 0.5615 0.5677
300 0.5102 0.5376 0.5484 0.5540
400 0.4991 0.5219 0.5343 0.5395
500 0.4907 0.5128 0.5224 0.5272
630 0.4827 0.5012 0.5101 0.5161

Inductance for three-core cable(reference value)
Nominal cross-section of conductor mm2 Rated voltages of cable(kV)
12/20 18/30 26/35
Inductance μH/km
25 - - -
35 0.4064 - -
50 0.3845 0.4396 0.4679
70 0.3620 0.4145 0.4427
95 0.3454 0.3956 0.4208
120 0.3392 0.3799 0.4019
150 0.3217 0.3642 0.3862
185 0.3145 0.3485 0.3737
240 0.3030 0.3360 0.3611
300 0.2935 0.3266 0.3485
400 0.2822 0.3041 0.3266
500 0.2742 - -
630 - - -