PRODUCT LIST
Home > Products > House Wiring & Equipment Wire > House Wiring & Equipment Wire
Flat cable

Description 

2 & 3 core flat, 450/750V V-90 insulated, PVC sheathed to AS/NZS 5000.2, copper conductors, 90°C.

Standards National :  AS/NZS 5000.2

Description                      

•2 & 3 core flat,

•450/750V V-90 insulated,

•PVC sheathed to AS/NZS 5000.2,

•Copper conductors, 90°C.


 

Table 

Type

No . of cores

×Nom. Cross

Section

mm2

No ./Dia.

of strand

mm

Nom.

Thickness

of insulation

mm

Nom.

thickness

of sheath

mm

Nominal overall 
diameter mm

Max.DC 
conductor

resistance 
at 20℃

Ω/km

Min. 
Insulating 
resistance

at 70℃

MΩ·km

Width

Height

Copper core

 

5000.2 

Flat cable

450/750V

2×1.0

1/1.37

0.6

0.9

6.5

4.2

18.1

17.0

2×1.5

7/0.52

0.6

0.9

7.2

4.5

13.6

14.0

2×2.5

7/0.68

0.7

1.0

8.9

5.4

7.41

12.0

2×4.0

7/0.85

0.8

1.1

10.5

6.3

4.61

12.0

2×6.0

7/1.04

0.8

1.1

11.6

6.9

3.08

9.9

2×10

7/1.33

1.0

1.2

14.2

8.3

1.83

9.9

2×16

7/1.70

1.0

1.3

16.3

9.5

1.4

8.4

 

 

 

 

 

 

 

 

2×1.0+E

1/1.37

0.6

0.9

8.9

4.2

18.1

17.0

2×1.5+E

7/0.52

0.6

0.9

9.9

4.5

12.1

14.0

2×2.5+E

7/0.68

0.7

1.0

12.2

5.4

7.41

12.0

2×4.0+E

7/0.85

0.8

1.1

13.9

6.3

4.61

12.0

2×6.0+E

7/1.04

0.8

1.1

15.0

6.9

3.08

9.9

2×10+E

7/1.33

1.0

1.2

18.3

8.3

1.83

9.9

2×16+E

7/1.70

1.0

1.3

21.0

9.5

1.4

8.4


PVC Surface Wiring

Specifications  BS6004 

Voltage Rating 0.3/0.5KV             

Description    Solid or Stranded plain copper conductor, 

PVC insulation, cores laid flat, PVC sheath

Type

No . of cores

×Nom. Cross

Section

mm2

Current rating 

Voltage drop 

Max.DC 
conductor

resistance 
at 20℃

Ω/km

 

Nominal 
overall 
diameter mm

 

 

 

Nominal weight 

KG/KM

Single 
phase ac 
or dc Amps

Three 
phase 
ac

Amps

Single 
phase ac 
or dc

mV/A/M

Three 
phase ac

mV/A/M

 

2×1.00+

15.00

-

44.00

-

18.10

4.20x6.50

52.00

2×1.50+

19.50

-

29.00

-

12.10

4.60X7.40

68.00

2×2.50+

27.00

-

18.00

-

7.41

5.40X8.80

101.00

2×4.00

36.00

-

11.00

-

4.61

6.10X10.20

146.00

2×6.00

46.00

-

7.30

-

3.08

6.90X11.50

202.00

2×10.00

63.00

-

4.40

-

1.83

8.20X14.00

319.00

2×16.00

85.00

-

2.80

-

1.15

9.40X16.20

468.00

 

3×1.00+

-

13.50

-

38.00

18.10

4.20X8.90

78.00

3×1.50+

-

17.50

-

25.00

12.10

4.60X10.20

99.00

3×2.50+

-

24.00

-

15.00

7.41

5.40X12.20

150.00

3×4.00

-

32.00

-

9.50

4.61

6.10X14.50

218.00

3×6.00

-

41.00

-

6.40

3.08

6.90X16.20

291.00

3×10.00

-

57.00

-

3.80

1.83

8.20X19.80

460.00

3×16.00

-

76.00

-

2.40

1.15

9.40X22.90

653.00

 

H03VVH2-F (flat cable)

300/300V

DIN VDE 0281-5, BS 6500, HD 21.5, 

NF C 32-201-5

APPLICATION

In domestic premises, kitchens, offices; for household appliances, including in damp premises; 
for medium duties (eg. washing machines, spin dryers, 
and refrigerators).  

No. and nom. 
cross-sec. area of 
conductors

No. and
dia. of 
strands

Thickness
of
insulation

Thickness 
of sheath

Mean overall  diameter

Max. DC 
resistance 
of 
conductor
at 20℃

Min. 
insulation
resistance
at 70℃

Lower 

limit

Upper

limit

(mm2)

(no./mm)

(mm)

(mm)

(mm)

(mm)

(Ω/km)

(MΩ.km)

H03VVH2-F

2x0.5

16/0.20

0.5

0.6

3.0x4.9

3.7x5.9

39.0

0.011

2x0.75

24/0.20

0.5

0.6

3.2x5.2

3.8x6.3

26.0

0.010

 

H03V2V2H2-F 

300/300V

DIN VDE 0281-5, BS 6500, HD 21.5, 

NF C 32-201-5

APPLICATION

In domestic premises, kitchens, offices; in high ambient temperatures 
for household appliances, including in damp premises; for medium duties 
(eg. washing machines, spin dryers, and refrigerators).

 

No. and nom. 
cross-sec. area of 
conductors

No. and
dia. of 
strands

Thickness
of
insulation

Thickness of
sheath

Mean overall diameter

Max. DC 
resistance 
of conductor
at 20℃

Min. 
insulation
resistance
at 90℃

Lower 

limit

Upper

limit

(mm2)

(no./mm)

(mm)

(mm)

(mm)

(mm)

(Ω/km)

(MΩ.km)

H03V2V2H2-F

2x0.5

16/0.20

0.5

0.6

3.0x4.9

3.7x5.9

39.0

0.011

2x0.75

24/0.20

0.5

0.6

3.2x5.2

3.8x6.3

26.0

0.010

 

 

H05VVH2-F 

300/500V

DIN VDE 0281-5, BS 6500, BS7919, HD 21.5, 

NF C 32-201-5

APPLICATION

In domestic premises, kitchens, offices; for household appliances, 
including in damp premises; for medium duties 
(eg. washing machines, spin dryers, and refrigerators).

No. and nom. 
cross-sec. area of 
conductors

No. and
dia. of 
strands

Thickness of
insulation

Thickness 
of sheath

Mean 

overall 
diameter

Max. DC 
resistance 
of conductor
at 20℃

Min. 
insulation
resistance
at 70℃

Lower limit

Upper limit

(mm2)

(no./mm)

(mm)

(mm)

(mm)

(mm)

Ω/km

(MΩ.km)

H05VVH2-F

2x0.75

24/0.2

0.6

0.8

3.7x6.0

4.5x7.2

26.0

0.011

2x1.0

32/0.2

0.6

0.8

3.9x6.2

4.7x7.5

19.5

0.010

2x1.5

30/0.25

0.7

0.8

4.2x7.0

5.2x8.6

13.3

0.010

 

 

H05V2V2H2-F 

300/500V

DIN VDE 0281-12, BS 6500, BS7919, HD 21.12

APPLICATION

In domestic premises, kitchens, and offices; in high ambient temperatures for household appliances, 
including in damp premises; for medium duties (eg. washing machines, spin dryers, and refrigerators).

No. and nom. 
cross-sec. area 
of conductors

No. and
dia. of strands

Thickness of
insulation

Thickness of
sheath

Mean  overall diameter

Max. DC 
resistance 
of conductor
at 20℃

Min. 
insulation
resistance
at 90℃

Lower limit

Upper limit

(mm2)

(no./mm)

(mm)

(mm)

(mm)

(mm)

Ω/km

(MΩ.km)

H05V2V2H2-F

2x0.75

24/0.2

0.6

0.8

3.7x6.0

4.5x7.2

26.0

0.011

2x1.0

32/0.2

0.6

0.8

3.9x6.2

4.7x7.5

19.5

0.010

2x1.5

30/0.25

0.7

0.8

4.2x7.0

5.2x8.6

13.3

0.010

 

Low Smoke Zero Halogen Surface Wiring

Specifications BS7211 

Voltage Rating 0.3/0.5KV

Description Solid or stranded plain copper conductor,

XLPE insulation, cores laid flat with a non-insulated circuit protective conductor, LSZH sheath

No . of 
cores ×Nom. 
Cross
Section
mm2

Nominal 
cross 
sectional 
area 
of CPC
Mm2

Current rating 

Voltage drop 

Max.DC
conductor
resistance
 at 20℃
Ω/km

 

Nominal 
overall 
diameter 
mm

 

Nominal 
weight
KG/KM

Single 
phase 
ac or 
dc Amps

Three 
phase 
ac
Amps

Single 
phase 
ac or dc
mV/A/M

Three 
phase 
ac
mV/A/M

2×1.00+

1.00+

19.00

-

46.00

-

18.10

4.40X8.10

68

2×1.50+

1.00+

24.00

-

31.00

-

12.10

4.70X8.60

76

2×2.50+

1.50+

33.00

-

19.00

-

7.41

5.30X9.80

109

2×4.00

1.50+

45.00

-

12.00

-

4.61

6.00X11.20

148

2×6.00

2.50+

58.00

-

7.90

-

3.08

6.70X12.90

209

2×10.00

4.00

80.00

-

4.70

-

1.83

7.60X15.20

320

2×16.00

6.00

107.00

-

2.90

-

1.15

8.80X18.00

474

3×1.00+

1.00+

-

17.00

-

40.00

18.10

4.40X10.70

86

3×1.50+

1.00+

-

22.00

-

27.00

12.10

4.70X11.40

117

3×2.50+

1.50+

-

30.00

-

16.00

7.41

5.30X12.80

143

3×4.00

1.50+

-

40.00

-

10.00

4.61

6.00X15.10

208

3×6.00

2.50+

-

52.00

-

6.80

3.08

6.70X17.40

292

3×10.00

4.00

-

71.00

-

4.00

1.83

7.60X20.50

446

3×16.00

6.00

-

96.00

-

2.50

1.15

8.80X24.10

664

+ means the cable is in solid conductor 

Description 

Flat travelling PVC cables for elevators

Standards 

International :  EN 50214;HD 359 S3;IEC 60332-1
National :  CSA C22.2 N° 49;DIN VDE 0281 part 404;UL 62

Description

Flat travelling PVC cables for elevators, for indoor applications, with a freely suspended length up to 35 meters.

Type

No . of
cores
×Nom.
Cross
Section
mm2

Insulation
 & sheath

Overall 
diameter 
size mm

Ohmical 
resistance
of the 
insulation
MOhm.km

Freely 
suspended
length M

Chemical 
resistance

Approximate
weight 
KG/KM

 

H05VVH6-F
300 / 500V

12×0.75

PVC

4.10X36.20

350

50

Restricted 
to oil, 
acid & base

236

16×0.75

PVC

4.10X42.30

350

50

Restricted 
to oil, 
acid & base

312

18×0.75

PVC

4.10X47.40

350

50

Restricted 
to oil, 
acid & base

353

20×0.75

PVC

4.30X54.00

350

50

Restricted 
to oil, 
acid & base

382

24×0.75

PVC

4.10X62.50

350

50

Restricted 
to oil, 
acid & base

465

6×1.0

PVC

4.60X20.60

350

50

Restricted 
to oil, 
acid & base

163

12×1.0

PVC

4.60X36.20

350

50

Restricted 
to oil, 
acid & base

302

16×1.0

PVC

4.30X45.50

350

50

Restricted 
to oil, 
acid & base

350

18×1.0

PVC

4.60X52.80

350

50

Restricted 
to oil, 
acid & base

443

20×1.0

PVC

4.60X59.00

350

50

Restricted 
to oil, 
acid & base

523

 

 

Description 

Flat travelling PVC cables for elevators, cold resistant with support elements.

Standards

International :  EN 50214;HD 359 S3;IEC 60332-1
National :  CSA C22.2 N° 49;DIN VDE 0281 part 404;UL 62

Description

Flat travelling cold resistant PVC cables for elevators, for indoor and outdoor applications, with a freely suspended length up to 75 meters.

Type

No . of
cores
×Nom. 
Cross
Section
mm2

Insulation
& sheath

Overall
diameter 
size mm

Maximum
operating
temperature 
°C

Minimum
operating
temperature
°C

Chemical 
resistance

Approximate
weight 
KG/KM

H05V3V3D3H6
-F300 / 500 V

24×0.75

PVC

4.10X67.40

70

-35

Restricted
to oil, 
acid 
& base

495

 

Description 

International Designation :  H05V3V3H6-F

Flat travelling PVC cables for elevators, cold resistant. 

Standards

International :  EN 50214; HD 359 S3; IEC 60332-1

Description

Flat travelling cold resistant PVC cables for elevators, for indoor and outdoor applications, with a freely suspended length up to  50 meters.

Type

No . of
cores
×Nom.
Cross
Section
mm2

Insulation
 & sheath

Overall 
diameter
size mm

Ohmical 
resistance 
of the
insulation
MOhm.km

Freely 
suspended
length M

Chemical
resistance

Approximate
weight 
KG/KM

 

H05V3V3H6-
 300 / 500 V

12×0.75

PVC

4.10X36.20

350

50

Restricted 
to oil, 
acid 
& base

236

    © 2013 Jiangsu Ganghong Electric Wire & Power Cable Co., Ltd. All Rights Reserved.